Issue |
Cause |
Solution |
---|---|---|
The actual motor speed does not correspond to speed reference. |
Preset speeds configuration interferes with speed reference from controller. |
Disable preset speeds in application functions setting of the drive. |
The actual motor speed does not correspond to speed reference. |
Limit switch configuration interferes with speed reference from controller. |
Disable limit switch function in application functions setting of the drive. |
The actual motor speed or read actual speed do not correspond to speed reference. |
PDO mapping is inconsistent. |
Make sure that both speed reference and actual speed values have the same unit (Hz or RPM). |
The brake is excessively stressed when starting hoisting movement in downwards direction. |
Brake impulse is not active. |
Activate brake impulse in Application functions – Brake logic of the Altivar drive. |