Type |
EF |
Devices supporting the parameter |
Safety Logic Controller TM5CSLCx00FS, Bus Interface TM5NS31, Sercos I/O |
Traceable |
– |
Enables the outputs of the I/O modules.
The parameter additionally starts the cyclic safety communication at the Safety Logic Controller and the bus interface.
Value |
Data type |
Meaning |
---|---|---|
off / 0 |
BOOL |
The outputs of the I/O modules are disabled. |
on / 1 |
BOOL |
The outputs of the I/O modules are enabled. |