Specifications

 

Specification

Value

Power Supply

Rated input voltage

24 Vdc

Input voltage limits

20.4...28.8 Vdc

Acceptable voltage drop

≤ 1 ms with lowest input voltage

≤ 10 ms with rated input voltage

Power consumption

HMIGXO3501: 5.7 W

HMIGXO3502: 8.7 W

HMIGXO5502: 11.3 W

In-rush current

≤ 50 A 1

Voltage endurance between power terminal and functional ground (FG)

600 Vac 20 mA for 1 min.

Insulation resistance between power terminal and FG.

10 MΩ or higher at 500 Vdc

Physical

Ambient operating temperature (cabinet interior & panel face)

0...50 °C (32...122 °F)

Storage temperature

-20...60 °C (-4...140 °F)

Relative humidity

85 % w/o condensation (Non condensing, wet bulb temperature 39  °C (102.2 °F) or less)

Air purity (dust)

≤ 0.1 mg/m3 (3.5-6 oz/ft3) (non-conductive levels)

Pollution degree

2

Corrosive gases

Free of corrosive gases

Atmospheric pressure

800...1,114 hPa (2,000 m (6561 ft) or less)

Mechanical

Vibration immunity

IEC 60068- 2 - 6

5...150 Hz, 3.5 mm (0.38 in) max., 1 g on 3 axes.

Shock immunity

IEC 60068 - 2 - 27

1/2 sinusoidal pulse for 11 ms, 15 g on 3 axes

Structural

Protection (front panel)

IP 65 - (IEC 60529)

Enclosure type 4 indoor use only (UL 50) with screw installation fasteners

Protection (rear panel)

IP 20 - (IEC 60529)

Electrical

Radiated radio frequency electromagnetic field

10 V/m / 80 MHz...1 GHz, 3 V/m / 1.4 MHz...2 GHz, 1 V/m / 2 GHz...3 GHz, sinus amplitude modulated 80 % / 1 kHz and internal clock frequency

Electrical fast transient

EN/IEC 61131-2 Zone B

2 kV power supply and 1 kV shielded cables

High energy surges

IEC 61000 - 4 - 5

0.5 kV (Differential Mode on power supply)

1 kV (Common Mode on power supply)

Electrostatic discharge Immunity

EN/IEC 61131-2

4 kV contact, 8 kV air

1 For in-rush current, the FWHM (full-width, half maximum) value is approximately 50 μs (when exceeding 25 A).

The front face of the panel, installed in a solid panel, has been tested using conditions equivalent to the standards shown in the specification.

Caution_Color.gifCAUTION

EQUIPMENT DAMAGE

Ensure that the panel is not in permanent and direct contact with oils.

Failure to follow these instructions can result in injury or equipment damage.

NOTICE

STORAGE AND OPERATION OUTSIDE OF SPECIFICATIONS

oStore the panel in areas where temperatures are within the panel's specifications.

oDo not restrict or block the panel's rear-face ventilation slots.

Failure to follow these instructions can result in equipment damage.

NOTICE

GASKET AGING

oInspect the gasket periodically as required by your operating environment to keep the initial IP level.

oChange the gasket at least once a year, or as soon as scratches or dirt become visible.

Failure to follow these instructions can result in equipment damage.

Air quality requirements

Do not operate or store the panel where any of the following chemicals may evaporate or where these chemicals are present in the air:

oCorrosive chemicals such as acids, alkalines and liquids containing salt.

oFlammable chemicals such as organic solvents.

Caution_Color.gifCAUTION

INOPERATIVE EQUIPMENT

Do not allow water, liquids, metal, and wiring fragments to enter the panel case.

Failure to follow these instructions can result in injury or equipment damage.