About the Book

Document Scope

This manual describes the hardware implementation of the Modicon TM5/TM7 Safety I/O modules. It provides part descriptions, specifications, wiring diagrams, installation and configuration information for Modicon TM5/TM7 Safety I/O modules.

Validity Note

This document has been updated for the release of EcoStruxure™ Machine Expert V2.2.

The technical characteristics of the devices described in the present document also appear online. To access the information online, go to the Schneider Electric home page at www.se.com.

The characteristics that are described in the present document should be the same as those characteristics that appear online. In line with our policy of constant improvement, we may revise content over time to improve clarity and accuracy. If you see a difference between the document and online information, use the online information as your reference.

Related Documents

Document title

Reference

Modicon TM5 Expansion Modules Configuration Programming Guide

EIO0000000420 (ENG);

EIO0000000421 (FRE);

EIO0000000422 (GER);

EIO0000000423 (SPA);

EIO0000000424 (ITA);

EIO0000000425 (CHS)

TM5SD•••FS Instruction Sheet

S1A85744

TM7SDI8DFS Instruction Sheet

NVE30386

TM7SDM12DTFS Instruction Sheet

S1A85745

TM5STI4ATCFS / TM5SAI4AFS Instruction Sheet

NVE30385

TM5SDC1FS Instruction Sheet

NVE30379

TM5SPS10FS Instruction Sheet

NVE30381

TM5CSLC• /TM5ACSLCM•• Instruction Sheet (TM5CSLC100FS / TM5CSLC200FS)

S1A85742

TM5CSLC300FS / TM5CSLC400FS / TM5ACSLCM8FS Instruction Sheet

NNZ96445

Modicon TM7 Digital I/O Blocks Hardware Guide

EIO0000000703 (ENG);

EIO0000000704 (FRE);

EIO0000000705 (GER);

EIO0000000706 (SPA);

EIO0000000707 (ITA);

EIO0000000704 (CHS)

Modicon TM5 Safety Logic Controller TM5CSLC•00FS Hardware Guide

EIO0000000889 (ENG);

EIO0000000890 (FRE);

EIO0000000891 (GER);

EIO0000000892 (ITA);

EIO0000000893 (SPA);

EIO0000000894 (CHS)

PacDrive TM5 / TM7 Safety Flexible System, System Planning and Installation Guide

EIO0000001064 (ENG);

EIO0000001066 (GER)

Modicon TM5 / TM7 Flexible System - System Planning and Installation Guide

EIO0000000426 (ENG);

EIO0000000427 (FRE);

EIO0000000428 (GER);

EIO0000000430 (ITA);

EIO0000000429 (SPA);

EIO0000000431 (CHS)

PacDrive Logic Motion Controller LMC Pro/Pro2 Hardware Guide

EIO0000001503 (ENG);

EIO0000001504 (GER)

Operating Manual TM5 SERCOS III Bus Interface

EIO0000002367 (ENG);

EIO0000002368 (GER)

EcoStruxure Machine Expert - Safety User Guide

EIO0000002147 (ENG);

EIO0000002148 (GER);

EIO0000004294 (ITA)

Safety Modules - Reference Guide

EIO0000002265 (ENG);

EIO0000002266 (GER);

EIO0000004295 (ITA)

M262 Embedded Safety - Integration Guide

EIO0000003921 (ENG);

EIO0000003923 (FRE);

EIO0000003922 (GER);

EIO0000003926 (SPA);

EIO0000003924 (ITA);

EIO0000003925 (CHS)

Modicon M262 Logic/Motion Controller Hardware Guide

EIO0000003659 (ENG);

EIO0000003660 (FRE);

EIO0000003661 (GER);

EIO0000003662 (SPA);

EIO0000003663 (ITA);

EIO0000003664 (CHS)

Cybersecurity Guidelines for EcoStruxure Machine Expert, Modicon and PacDrive Controllers and Associated Equipment, User Guide

EIO0000004242 (ENG)

Refer to the online help for other related documentation.

Product Related Information

For important hazardous location information, refer to the individual product descriptions contained in the present document.

 DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
  • Disconnect all power from all equipment including connected devices prior to removing any covers or doors, or installing or removing any accessories, hardware, cables, or wires except under the specific conditions specified in the appropriate hardware guide for this equipment.
  • Always use a properly rated voltage sensing device to confirm the power is off where and when indicated.
  • Replace and secure all covers, accessories, hardware, cables, and wires and confirm that a proper ground connection exists before applying power to the unit.
  • Use only the specified voltage when operating this equipment and any associated products.
Failure to follow these instructions will result in death or serious injury.
 WARNING
LOSS OF CONTROL
  • Perform a Failure Mode and Effects Analysis (FMEA), or equivalent risk analysis, of your application, and apply preventive and detective controls before implementation.
  • Provide a fallback state for undesired control events or sequences.
  • Provide separate or redundant control paths wherever required.
  • Supply appropriate parameters, particularly for limits.
  • Review the implications of transmission delays and take actions to mitigate them.
  • Review the implications of communication link interruptions and take actions to mitigate them.
  • Provide independent paths for control functions (for example, emergency stop, over-limit conditions, and error conditions) according to your risk assessment, and applicable codes and regulations.
  • Apply local accident prevention and safety regulations and guidelines.1
  • Test each implementation of a system for proper operation before placing it into service.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

1 For additional information, refer to NEMA ICS 1.1 (latest edition), Safety Guidelines for the Application, Installation, and Maintenance of Solid State Control and to NEMA ICS 7.1 (latest edition), Safety Standards for Construction and Guide for Selection, Installation and Operation of Adjustable-Speed Drive Systems or their equivalent governing your particular location.

 WARNING
UNINTENDED EQUIPMENT OPERATION
  • Only use software approved by Schneider Electric for use with this equipment.
  • Update your application program every time you change the physical hardware configuration.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
 WARNING
UNINTENDED EQUIPMENT OPERATION
  • Understand the requirements contained in IEC 61508, "Functional safety of electrical/electronic/programmable electronic safety-related systems" before applying the information contained in the present document.
  • Completely understand the applications and environment defined by Safety Integrity Level (SIL) 3 within IEC 61508 Parts 1-7.
  • Do not exceed SIL 3 ratings in the application of this product.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
 WARNING
POTENTIAL OF OVERHEATING AND FIRE
  • Do not connect the equipment directly to line voltage.
  • Use only isolating power supplies to supply power to the modules.
  • Consult the present document for these products for correct voltage and current limits.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

Terminology Derived from Standards

The technical terms, terminology, symbols and the corresponding descriptions in this manual, or that appear in or on the products themselves, are generally derived from the terms or definitions of international standards.

In the area of functional safety systems, drives and general automation, this may include, but is not limited to, terms such as safety, safety function, safe state, fault, fault reset, malfunction, failure, error, error message, dangerous, etc.

Among others, these standards include:

Standard

Description

IEC 61131-2:2007

Programmable controllers, part 2: Equipment requirements and tests.

ISO 13849-1:2015

Safety of machinery: Safety related parts of control systems.

General principles for design.

EN 61496-1:2013

Safety of machinery: Electro-sensitive protective equipment.

Part 1: General requirements and tests.

ISO 12100:2010

Safety of machinery - General principles for design - Risk assessment and risk reduction

EN 60204-1:2006

Safety of machinery - Electrical equipment of machines - Part 1: General requirements

ISO 14119:2013

Safety of machinery - Interlocking devices associated with guards - Principles for design and selection

ISO 13850:2015

Safety of machinery - Emergency stop - Principles for design

IEC 62061:2015

Safety of machinery - Functional safety of safety-related electrical, electronic, and electronic programmable control systems

IEC 61508-1:2010

Functional safety of electrical/electronic/programmable electronic safety-related systems: General requirements.

IEC 61508-2:2010

Functional safety of electrical/electronic/programmable electronic safety-related systems: Requirements for electrical/electronic/programmable electronic safety-related systems.

IEC 61508-3:2010

Functional safety of electrical/electronic/programmable electronic safety-related systems: Software requirements.

IEC 61784-3:2016

Industrial communication networks - Profiles - Part 3: Functional safety fieldbuses - General rules and profile definitions.

2006/42/EC

Machinery Directive

2014/30/EU

Electromagnetic Compatibility Directive

2014/35/EU

Low Voltage Directive

In addition, terms used in the present document may tangentially be used as they are derived from other standards such as:

Standard

Description

IEC 60034 series

Rotating electrical machines

IEC 61800 series

Adjustable speed electrical power drive systems

IEC 61158 series

Digital data communications for measurement and control – Fieldbus for use in industrial control systems

Finally, the term zone of operation may be used in conjunction with the description of specific hazards, and is defined as it is for a hazard zone or danger zone in the Machinery Directive (2006/42/EC) and ISO 12100:2010.

NOTE: The aforementioned standards may or may not apply to the specific products cited in the present documentation. For more information concerning the individual standards applicable to the products described herein, see the characteristics tables for those product references.