8342 On/OffPos inverted (On/OffDelay ok?)
Refer to Diagnostic class (standard): 3
CamSwitch.OnPosition and CamSwitch.OffPosition switched their relative position due to velocity compensation with the configured delay
|
Cause |
Solution |
|---|---|
|
CamSwitch.OnPosition and CamSwitch.OffPosition are too close together for the present speed and the difference of the entered delay times of the corresponding CamTrack.OnDelay and CamTrack.OffDelay. |
oReduce velocity. oReduce delay difference. oIncrease position difference. |