BITADR

Overview

This address operator is not specified by the standard IEC 61131-3.

BITADR returns the bit offset within the segment in a DWORD. The offset value depends on whether the option Byte addressing in the target settings is activated or not.

The highest nibble in that DWORD indicates the memory area:

Memory: 16x40000000

Input: 16x80000000

Output: 16xC0000000

Example in ST

VAR
        var1 AT %IX2.3:BOOL;
        bitoffset: DWORD;
END_VAR
bitoffset:=BITADR(var1); (* Result if byte addressing=TRUE: 16x80000013, if byte addressing=FALSE: 16x80000023 *)

Example in IL

LD     Var1
BITADR
ST     bitoffset

Considerations for Online Changes

Executing the Online Change command can change the contents of addresses.

Caution_Color.gifCAUTION

INVALID POINTER

Verify the validity of the pointers when using pointers on addresses and executing the Online Change command.

Failure to follow these instructions can result in injury or equipment damage.