ETH_R: Ethernet Port Read-Only System Variables
This table describes the parameters of the ETH_R system variable (ETH_R_STRUCT type):
|
%MW |
Var Name |
Type |
Comment |
|---|---|---|---|
|
60050 |
i_byIPAddress[0..3] |
ARRAY[0..3] OF BYTE |
IP address [aaa.bbb.ccc.ddd]: oi_byIPAddress[0] = aaa o... oi_byIPAddress[3] = ddd |
|
60052 |
i_bySubNetMask[0..3] |
ARRAY[0..3] OF BYTE |
Subnet Mask [aaa.bbb.ccc.ddd]: oi_bySub-netMask[0] = aaa o... oi_bySub-netMask[3] = ddd |
|
60054 |
i_byGateway[0..3] |
ARRAY[0..3] OF BYTE |
Gateway address [aaa.bbb.ccc.ddd]: oi_byGateway[0] = aaa o... oi_byGateway[3] = ddd |
|
60056 |
i_byMACAddress[0..5] |
ARRAY[0..5] OF BYTE |
MAC address [aa.bb.cc.dd.ee.ff]: oi_byMACAddress[0] = aa o... oi_byMACAddress[5] = ff |
|
60059 |
i_sDeviceName |
STRING(16) |
Name used to get IP address from server. |
|
n/a |
i_wIpMode |
Method used to obtain an IP address. |
|
|
n/a |
i_byFDRServerIPAddress[0..3] |
ARRAY[0..3] OF BYTE |
The IP address [aaa.bbb.ccc.ddd] of the DHCP or BootP server: oi_byFDRServerIPAddress[0] = aaa o... oi_byFDRServerIPAddress[3] = ddd Equals 0.0.0.0 if Stored IP or Default IP used. |
|
n/a |
i_udiOpenTcpConnections |
UDINT |
Number of open TCP connections. |
|
n/a |
i_wFrameSendingProtocol |
Ethernet protocol configured for frames sending (IEEE 802.3 or Ethernet II). |
|
|
n/a |
i_udiFramesTransmittedOK |
UDINT |
Number of frames successfully transmitted. Reset at Power ON or with reset command ETH_W.q_wResetCounter. |
|
n/a |
i_udiFramedReceivedOK |
UDINT |
Number of frames successfully received. Reset at Power ON or with reset command ETH_W.q_wResetCounter. |
|
n/a |
i_udiTransmitBufferErrors |
UDINT |
Numbers of frames transmitted with detected errors. Reset at Power ON or with reset command ETH_W.q_wResetCounter. |
|
n/a |
i_udiReceiveBufferErrors |
UDINT |
Numbers of frames received with detected errors. Reset at Power ON or with reset command ETH_W.q_wResetCounter. |
|
n/a |
i_wPortALinkStatus |
Link of the Ethernet Port (0 = No Link, 1 = Link connected to another Ethernet device). |
|
|
n/a |
i_wPortASpeed |
Ethernet Port network speed (10Mb/s, 100Mb/s). |
|
|
n/a |
i_wPortADuplexStatus |
Ethernet Port duplex status (0 = Half or 1 = Full duplex). |
|
|
n/a |
i_udiPortACollisions |
UDINT |
Number of frames involved in one or more collisions and subsequently transmitted successfully. Reset at Power ON or with reset command ETH_W.q_wResetCounter. |
|
Modbus TCP/IP Specific |
|||
|
n/a |
i_udiModbusMessageTransmitted |
UDINT |
Number of Modbus messages transmitted. Reset at Power ON or with reset command ETH_W.q_wResetCounter. |
|
n/a |
i_udiModbusMessageReceived |
UDINT |
Number of Modbus messages received. Reset at Power ON or with reset command ETH_W.q_wResetCounter. |
|
n/a |
i_udiModbusErrorMessage |
UDINT |
Modbus detected error messages transmitted and received. Reset at Power ON or with reset command ETH_W.q_wResetCounter. |
|
n/a means that there is no predefined %MW mapping for this system variable. |
|||
NOTE: n/a means that there is no predefined %MW mapping for this system variable.