IF_ConfigurationAdvanced - SetTrackingParameters (Method)

Overview

Type:

Method

Available as of:

V2.10.0.0

This chapter provides information on:

Task

Setting a set of parameters for a specific tracking system.

Description

With the method SetTrackingParameters(…), a set of parameters can be applied to a specific tracking system.

Interface

Input

Data type

Description

i_etTrackingSystem

ROB.ET_CoordinateSystem

Tracking system for which the parameters should be set.

Valid value: Identifier of a configured tracking system.

i_stParameters

ROB.ST_TrackingParameters

Parameters that should be applied to the tracking system transferred at input i_etTrackingSystem.

Output

Data type

Description

q_etDiag

GD.ET_Diag

General library-independent statement on the diagnostic.

A value not equal to GD.ET_Diag.Ok corresponds to a diagnostic message.

q_etDiagExt

ET_DiagExt

POU-specific output on the diagnostic.

q_etDiag = ET_Diag.Ok -> Status message

q_etDiag <> ET_Diag.Ok -> Diagnostic message

q_sMsg

STRING[80]

Event-triggered message that gives additional information on the diagnostic state.

Diagnostic Messages

q_etDiag

q_etDiagExt

Enumeration value

Description

OK

Ok

0

Ok

InputParameterInvalid

CoordinateSystemInvalid

93

The coordinate system is invalid.

InputParameterInvalid

CoordinateSystemNotConfigured

268

The coordinate system is not configured.

InputParameterInvalid

AccelerationZeroThresholdRange

372

The value of ROB.ST_TrackingParameters.lrAccelerationZeroThreshold is out of range.

UnexpectedProgramBehavior

UnexpectedFeedback

28

A feedback value was invalid.

AccelerationZeroThresholdRange

Enumeration name:

AccelerationZeroThresholdRange

Enumeration value:

372

Description:

The value of ROB.ST_TrackingParameters.lrAccelerationZeroThreshold is out of range.

Issue

Cause

Solution

Setting the tracking parameters was not successful.

The value transferred at the input i_stParameters. lrAccelerationZeroThreshold lies outside the valid range.

At the input i_stParameters. lrAccelerationZeroThreshold, a value greater or equal to 0.0 or equal to -1.0 must be transferred.

CoordinateSystemInvalid

Enumeration name:

CoordinateSystemInvalid

Enumeration value:

93

Description:

The coordinate system is invalid.

Issue

Cause

Solution

Setting the tracking parameters was unsuccessful.

The value transferred at the input i_etTrackingSystem does not represent a tracking system.

Verify that at the input i_etTrackingSystem a configured tracking system is transferred, and correct if necessary.

CoordinateSystemNotConfigured

Enumeration name:

CoordinateSystemNotConfigured

Enumeration value:

268

Description:

The coordinate system is not configured.

Issue

Cause

Solution

Setting the tracking parameters was unsuccessful.

The value transferred at the input i_etTrackingSystem does not represent a configured tracking system.

Verify that at the input i_etTrackingSystem a configured tracking system is transferred, and correct if necessary.

Ok

Enumeration name:

Ok

Enumeration value:

0

Description:

Ok

Setting the tracking parameters was successful.

UnexpectedFeedback

Enumeration name:

UnexpectedFeedback

Enumeration value:

28

Description:

A feedback value was invalid.

Setting the tracking parameters was unsuccessful. A feedback value was invalid.