Refer to Diagnostic class (standard): 1
Default reaction |
||
---|---|---|
E |
E |
This diagnostic message relates to the multi carrier transport system.
A logger entry in the segment is triggered indicating that a cybersecurity device unlock/lock operation was performed.
For in-depth diagnosis, a cybersecurity device unlock/lock operation can be performed by authorized and qualified personnel (Schneider Electric field application engineer).
Segments are shipped by Schneider Electric in the cybersecurity device state “locked”.
If the cybersecurity device state of a segment is set to "unlocked", the segment can potentially be accessed without authorization.
WARNING | |
---|---|
Information on the cybersecurity device state is provided by three parameters of the segment logger entry:
Parameter 1 (device lock/unlock attempt):
1 = device lock/unlock attempt was successful
0 = device lock/unlock attempt was unsuccessful
Parameter 2 (new lock state):
0 = device locked
255 = device unlocked
Other values are for test purposes only.
Parameter 3 (previous lock state):
0 = device locked
255 = device unlocked
Other values are for test purposes only.
Examples:
Successful unlock:
Parameter 1 = 1
Parameter 2 = 255
Parameter 3 = is not relevant
Successful lock:
Parameter 1 = 1
Parameter 2 = 0
Parameter 3 = is not relevant