The menu item “Duplicate” allows you to copy the eSM parameters and parameter values of a safety module eSM to another safety module eSM.
| WARNING | |
|---|---|
This function can be used, for example, in the following scenarios:
Production of multiple, identical machines
Replacement of a safety module eSM
The eSM parameters are transferred from a safety module eSM to a storage medium or from a storage medium to a safety module eSM in the form of a file.
It is not possible to modify individual parameter values with the “Duplicate” function.
eSM parameters can be duplicated under the following conditions:
Expert mode must be active in the commissioning software.
The eSM standard password must have been entered.
Refer to Menu Item “Change Password” for information on passwords.
Enter your eSM standard password to access the function “Duplicate”. The eSM standard password is verified by the safety module eSM. If the password is correct, you can duplicate the eSM parameters. Refer to Menu Item “Change Password” for information on passwords.
When you duplicate the eSM parameters, the eSM parameter password that is used to modify the eSM parameter values is saved along with the parameters. You can only modify parameter values after having entered the eSM parameter password.
eSM parameters are not stored on the memory card in the drive.
Verify correct commissioning before duplication.
A checksum is saved along with the configuration file to allow for identification of the duplicated eSM parameters. The checksum is displayed for verification purposes before an eSM parameter set is transferred to a safety module eSM.