Refer to Diagnostic class (standard): 2
Default reaction |
||
---|---|---|
- |
- |
|
D |
E |
The value of the parameter MainsVoltageMode is not set in accordance to the infeed voltage.
This alert is given out if at the end of the pre-charge phase the DC bus voltage is greater than 560 V (by MainsVoltageMode=230 V) or lower than 460 V (by MainsVoltageMode=400 V).
Cause |
Solution |
---|---|
The setting of the parameter MainsVoltageMode is incorrect. |
Verify and correct if necessary the parameters. |
Interruption of one or more phases of the mains feed-in. |
Verify and correct if necessary the wiring of the mains phases. |