Residual current measurement
The meter can calculate or measure the residual current, depending on how the inputs are wired.
3 CT wiring
|
For a 3-phase 3-wire system, the meter calculates residual current for Ground. For a 3-phase 4-wire system, the meter calculates residual current for Neutral. |
For a 3-phase 3-wire system, the meter measures the residual current for Ground at I4. For a 3-phase 4-wire system, the meter measures the residual current for Neutral at I4. |
|
|
4 CT wiring
|
For a 3-phase 4-wire system, the meter calculates residual current for Ground. |
For a 3-phase 4-wire system, the meter measures the residual current for Ground at I5. |
|
|