Creating custom webpages

Create custom webpages to view data or access configuration parameters from your meter.

Download the meter’s Modbus registers map from www.se.com.

  1. Open SFTP client software.
  2. Go to web > examples. Select samplereadings.html to create a data value webpage or select sampleconfiguration.html to create a configuration parameters webpage.
  3. Save a copy of the sample file. This filename is the webpage name.
  4. Open your webpage in an HTML or webpage editor program.
  5. Modify the webpage to reference the desired meter data or parameters from the Modbus registers map, and update the other fields where required.
  6. Save your custom webpage.

    The meter will display translated content if it exists in the meter’s memory. If translated content is not available, English is displayed.

  7. Connect to your meter’s internal SFTP site.
    • If you have created a data viewing webpage, copy your custom webpage to web > monitoring.
    • If you have created a configuration webpage, copy your custom webpage to web > setup.
  8. Login to your meter’s webpages.

Your custom webpage is available from the webpage menu under the Monitoring (data viewing) or Setup (configuration) tab.

Watch the video on how to create custom webpages: How to Create Custom Webpages for Your Meter