Configure Significant Change Properties

Use the fields within the Significant Change section of the Counter Point tab to define by how much a counter’s engineering value has to change in order for the SCADAPack E outstation to generate an event for the counter.

Use Significant Change to help prevent excessive database updates, by determining when a significant change in point value is included in the Geo SCADA Expert database, and when an insignificant change in value can be discarded (the database retains the previously recorded value).

The Significant Change feature applies only to current data (it does not apply to logged data). The driver applies the significant change Deadband whenever it receives a new current value for the point. The driver uses the Deadband to determine whether or not to pass the point update to the database server.