Configure Analog Points for DNP3 Communications

The topics in this section document the properties on the Forms of SCADAPack x70 DNP3 Analog Points. You only require such points if Geo SCADA Expert is to use the DNP3 protocol to communicate with a SCADAPack x70 device and is to perform either of the following:

  • Retrieve analog data from the SCADAPack x70 device
  • Set the values of analog data on the SCADAPack x70 device.

Geo SCADA Expert uses the points to store protocol-specific information about how it processes the point data that it retrieves from, or sends to, the device.

For each item of analog data that Geo SCADA Expert is to retrieve from a SCADAPack x70 device using the DNP3 protocol, you need to create and configure a SCADAPack x70 DNP3 Analog Input Point in the database.

For each item of analog data for which Geo SCADA Expert is to set the values on a SCADAPack x70 device using the DNP3 protocol, you need to create and configure a SCADAPack x70 DNP3 Analog Output Point in the database.

Instead of manually creating a SCADAPack x70 protocol-specific Point, you can use the Create Protocol Point pick action to create the point from the <Point Type> Configuration item with which it is to be associated. This means of point creation will associate the Point automatically with the <Point Type> Configuration item from which the pick action was triggered. For more information, including essential checks to perform before using the pick action, see Create Protocol Point.

Alternatively, you can automatically create a suite of SCADAPack x70 protocol-specific Points for each of the SCADAPack x70 <Point Type> Configuration items that are associated with a particular SCADAPack x70 Device Configuration item. To do this, you use the separate Create Protocol Points pick action on that SCADAPack x70 Device Configuration item. Again, this means of point creation with associate each automatically-created Point with the SCADAPack x70 <Point Type> Configuration item to which it relates on the SCADAPack x70 Device Configuration item. For more information, including essential checks to perform before using this pick action, see Create Protocol Points.

You configure the properties of each Point using the fields on the SCADAPack x70 DNP3 Analog Input Point or SCADAPack x70 DNP3 Analog Output Point Form respectively. Each Form has several tabs, some of which contain properties that are common to many database items, and others that contain properties that are specific to Analog Points.

This topic provides information about the properties that are on the Analog Point and Control tabs.

Use the Analog Point tab to:

The Analog Point tab also includes two sections of properties for which the settings are purely inherited from the SCADAPack x70 Analog Configuration item with which the Analog Point is associated:

These properties are merely included on the tab for reference when configuring other properties on the Analog Point's Form. For information about the properties from which the settings are inherited, select the links above and see SCADAPack x70 DNP3 Analog Point Inheritance. (If you have not re-opened this configuration Form since using the Form's SCADAPack x70 Object field to associate this Point with the relevant Configuration item, you may need to refresh the Form in order for these fields to display their inherited values. Likewise, if the inherited values are changed on that Configuration item's Form while this Point Form remains open, you might also need to refresh this Form to display the updated inherited values. To do this, save the configuration changes.)

The Forms of SCADAPack x70 DNP3 Analog Output Points also include a Control tab.

Use the Control tab to:

The properties on the remaining tabs are common to points on many drivers. For information about those tabs, see Tabs on Point Forms in the Geo SCADA Expert Guide to Advanced Drivers.

Further Information

Minimum Configuration - Points.