RS232 Communications

The table below summarizes RS232 serial communications characteristics when you select RS232, RS232 (RTS On) or RS232 (RTS Off) as the Port Mode.

Port Mode Function Characteristics
RS232 Operation Used for RS232 communications on serial ports that do not provide hardware control lines for Request to Send (RTS), Clear to Send (CTS), Data Terminal Ready (DTR) or Data Carrier Detect (DCD).
Interface Type DTE
Data Lines RX, TX, GND
Control Lines None
Speeds (bps) 300, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
R232 (RTS On) Operation

Used for RS232 communications where the Request to Send (RTS) signal needs to be constantly asserted. No hardware hand shaking is required or supported when this mode is selected.

Interface Type DTE
Data Lines RX, TX, GND
Control Lines RTS out (on), CTS in (ignored), ·DCD in (ignored)
Speeds (bps) 300, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
RS232 (RTS Off) Operation

Used for RS232 communications where the Request to Send (RTS) signal needs to be constantly deasserted. No hardware handshaking is required or supported when this mode is selected.

Interface Type DTE
Data Lines

RX, TX, GND

Control Lines RTS out (off), CTS in (ignored), ·DCD in (ignored)
Speeds (bps) 300, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200