8193 Machine encoder temperature is high
Refer to Diagnostic class (standard): 3
|
Default reaction |
||
|---|---|---|
|
D |
E |
|
|
- |
- |
The temperature inside the machine encoder is too high.
|
Cause |
Solution |
|---|---|
|
Insufficient ventilation or ambient temperature too high. |
Verify and correct or replace if necessary the device fans and ventilation slots (if available). |
|
Check ventilation in switching cabinet. |
If installed, ensure that the air conditioning unit is functioning properly. |
|
Detected hardware error: The temperature sensor is inoperable. |
Replace the device. |