8195 Machine encoder signal is out of range
Refer to Diagnostic class (standard): 3
Default reaction |
||
---|---|---|
AD |
AD |
|
– |
– |
A hardware encoder error has been detected. There is measured a voltage in the analog sinus or cosinus encoder tracks that is not matching the specified voltage range of the encoder.
Cause |
Solution |
---|---|
Detected wiring error: Encoder cable at the encoder or the servo amplifier / PacDrive controller has been removed or is inoperable. |
oVerify the encoder cable and replace if necessary. oVerify and correct if necessary the ground connection (shield). |
The encoder voltage is unavailable or incorrect. |
Verify and correct if necessary the encoder voltage. |
The control voltage of the device (24 Vdc) is too low. |
Verify and correct if necessary the control voltage. |
Detected hardware error: Encoder is inoperable. |
Replace the encoder. |