8055 Controller message HW monitor

Description

Refer to Diagnostic class (standard): 1

MsgFilter: Bit 14 Filter Type 15

Refer to the diagnostic messages 8056 Supply voltage low and 8827 Controller power-off/hardware monitor.

DiagMsg:

oSpecific diagnostic message for debugging purposes.

oStructure: <last error entry> : <error group> : <cause of error>

Error groups:

oVoltageError

oTempError

oEnvError

Cause of error (VoltageError):

oV3.3 < Vmin

oV5 < Vmin

oV+12 < Vmin

oV-12 < Vmin

oVin < Vshutd

oVAccu < Vshutd

oVin_jit < Vshutd

ocapacitance

oLTC error

oVin > Vmax

oVAccu > Vmax

oV3.3 > Vmax

oV5 > Vmax

oV+12 > Vmax

oV-12 > Vmax

oVcpuCore < Vmin

oVcpuIO < Vmin

oVM2.5 < Vmin

oVM3.3 < Vmin

oVM5 < Vmin

oVM+12 < Vmin

oVM-12 < Vmin

oVcpuCore > Vmax

oVcpuIO > Vmax

oVM2.5 > Vmax

oVM3.3 > Vmax

oVM5 > Vmax

oVM+12 > Vmax

oVM-12 > Vmax

Cause of error (TempError):

oVin < Vmin

oVAccu < Vmin

oTAccu < Tmin

oTLM75 < Tmin

oTCPU < Tmin

oTM1 < Tmin

oTM2 < Tmin

oTAccu > Tshutd

oTLM75 > Tshutd

oTCPU > Tshutd

oTM1 > Tshutd

oTM2 > Tshutd

oTAccu > Tmax

oTLM75 > Tmax

oTCPU > Tmax

oTM1 > Tmax

oTM2 > Tmax

oI2C bus failed

oLM75 failed

Cause of error (EnvError):

ofan1stop-shutd

ofan1stop-off

ofan2stop-shutd

ofan2stop-off

ofan3stop-shutd

ofan3stop-off

Example of message text:

-1 : TempError  : TLM75 > Tshutd

The error was in the last created error entry. It is a temperature error in which the LM75 sensor detected a temperature that is too high. The shutdown limit was exceeded, and so the system shut down after the timer ran out.