8104 Control voltage out of range
Refer to Diagnostic class (standard): 3
|
Default reaction |
||
|---|---|---|
|
BD2 |
CD |
|
|
BP1 |
BP1 |
This diagnostic message is triggered if the control voltage (24 Vdc) is not within the permitted range anymore.
The drive was stopped because an error-free function of the device could no longer be affirmed.
|
Cause |
Solution |
|---|---|
|
The control voltage is too high or too low. |
Verify and correct if necessary the control voltage (see technical data of the device). |