Refer to Diagnostic class (standard): 2
|
Default reaction |
||
|---|---|---|
|
D |
E |
|
|
- |
- |
An attempt is being made to start the drive, but Inverter_Enable is still LOW.
|
Cause |
Solution |
|---|---|
|
ControllerEnable is activated, but InverterEnable is still LOW. |
Verify and correct if necessary the wiring of InverterEnable. |
Probably it is normal machine behavior. If it is not allowed to switch off InverterEable during the axis is controlled, InverterEnableFunction has to be set to Safe Stop / 1.
|
Cause |
Solution |
|---|---|
|
The parameter InverterEnableFunction is set to Safe Torque Off / 0, the axis is moving, and the InverterEnable signals gets LOW. |
Probably it is normal machine behavior. If it is not allowed to switch off InverterEable during the axis is controlled, InverterEnableFunction has to be set to Safe Stop / 1. |