8139 DC bus precharge not possible

Description

Refer to Diagnostic class (standard): 3

Device reactions

Default reaction

Minimum reaction

Drive

-

-

Power supply

BP1

BP1

In the Lexium 62 Power Supply or Lexium 52, the detected error message is triggered if the pre-charge of the DC bus could not be completed after a predefined time, that is internally calculated with data from the device type plate. If this error is triggered, then the device has to be reset or turned off /on again.

Cause

Solution

An external load is connected to the DC bus.

Remove external load.

The parameter MainsVoltageMode is configured in an incorrect way.

Verify the parameter MainsVoltageMode and correct it, if necessary.

During the pre-charge, the mains phases were disconnected temporarily.

Verify if the cable for the mains connection is connected to the device correctly.