Refer to Diagnostic class (standard): 3
Default reaction |
||
---|---|---|
D |
E |
|
- |
- |
The temperature inside the motor encoder is too high.
Cause |
Solution |
---|---|
Insufficient ventilation or ambient temperature too high. |
Verify and correct if necessary the device fans and ventilation slots (if available). |
Check ventilation in switching cabinet. |
If installed, ensure that the air conditioning unit is functioning properly. |
Detected hardware error: The temperature sensor is inoperable. |
Replace the device. |