Refer to Diagnostic class (standard): 3
|
Default reaction |
||
|---|---|---|
|
- |
- |
|
|
BP1 |
BP1 |
The DC bus is overloaded. In this case, unlike diagnostic message 8107 Overcurrent, switch off does not occur as soon as the current threshold has been exceeded. The thermal overload of the device is observed for a specific time.
|
Cause |
Solution |
|---|---|
|
Too many loads are connected to the DC bus. |
oIt may be that the existing device constellation is sufficient by adapting the application (for example, less acceleration). oUse another power supply and distribute supply of loads. |