TM7BAI4PLA Presentation

Main Characteristics

The table below provides the main characteristics of the TM7BAI4PLA block:

Main characteristics

Number of input channels

4

Measurement type

Temperature

Input sensor type

J, K and S thermocouple sensors

Resolution

16 bits

Sensor connection type

M12, A coded, female connector type

The thermocouple blocks are configured as a whole for the same type of thermocouple sensor. You cannot mix thermocouple sensor types on the same block, otherwise the temperature readings will not be correct.

Warning_Color.gifWARNING

UNINTENDED EQUIPMENT OPERATION

oOnly connect thermocouple sensors of the same type to the temperature block.

oConfigure the block for the correct type of thermocouple.

Failure to follow these instructions can result in death, serious injury, or equipment damage.

Description

The following figure shows the TM7BAI4PLA block:

G-SE-0006514.1.gif

 

(A)   TM7 bus IN connector

(B)   TM7 bus OUT connector

(C)   24 Vdc power IN connector

(D)   24 Vdc power OUT connector

(1)   Input connectors

(2)   Status LEDs

Connector and Channel Assignments

The table below provides the connector and channel assignments of the TM7BAI4PLA block:

Input connectors

Input status LEDs

Channel type

Channels

1

1

Input

I0

2

2

Input

I1

3

3

Input

I2

4

4

Input

I3

Status LEDs

The following figure shows the status LEDs of the TM7BAI4PLA block:

G-SE-0006368.1.gif

 

(1)   TM7 bus status LEDs, set of two LEDs: 1.1 (green) and 1.2 (red)

(2)   Input status LEDs, composed of four LEDs: 1, 2, 3 and 4 (green)

(3)   Input block status LEDs, set of two LEDs: 3.1 (green) and 3.2 (red)

The table below provides the TM7 bus status LEDs of the TM7BAI4PLA block:

TM7 bus status LEDs

Description

LED 1.1

LED 1.2

OFF

OFF

No power supply on TM7 bus

ON

ON

TM7 bus in preoperational state:

opower supply on TM7 bus and

oblock not initialized

ON

OFF

TM7 bus in operational state

OFF

ON

TM7 bus error detected

The table below provides the input status LEDs of the TM7BAI4PLA block:

Channel LEDs

State

Description

1 - 4

OFF

Open connection or sensor is disconnected or not used

Flashing

Overflow or underflow of the input signal

ON

The analog/digital converter is running, a value is available

The table below provides the input block status LEDs of the TM7BAI4PLA block:

Block Status LEDs

State

Description

3.1

OFF

No power supply

Single Flash

Reset state

Flashing

Preoperational state

ON

Operational state

3.2

OFF

OK or no power supply

Single Flash

Detected error for an input channel. Overflow or underflow of the input signal

Double Flash

Power supply not in the valid range

ON

Detected error or reset state

Terminal Temperature (Cold Junction) Compensation

When using thermocouples, it is necessary to measure the temperature at the terminal connections of the TM7BAI4PLA in order to calculate an accurate absolute temperature at the measuring point of the thermocouple. The sensor used to measure the terminal temperature is integrated in the TM7ACTHA thermocouple connector.

NOTE: At least one terminal temperature sensor TM7ACTHA is required to determine the temperature measured by the connected thermocouples. Otherwise, a value of 7FFF hex is calculated for all the connected thermocouples.

The accuracy of the temperature measurement of the connected thermocouples is a function of the number of terminal temperature sensors connected to the block.

The table below provides examples for the possible configurations:

TM7ACTHA connected on the input connector

Description

1

The terminal temperature compensation for all 4 channels is performed using the temperature measured on connector 1.

1 and 3

The terminal temperature compensation for channels I0 and I1 is performed using the temperature measured on connector 1. The terminal temperature compensation for channels I2 and I3 is performed using the temperature measured on connector 3.

1, 2, 3 and 4

The terminal temperature compensation is performed using the temperature measured on the respective connector.

NOTE: For the correspondence between the connectors and channels, refer to Connector and Channel Assignments.

TM7ACTHA Presentation

The TM7ACTHA thermocouple plug is used for compensation of the temperature at measurements points. The sensor to measure the terminal temperature is integrated in the thermocouple plug.

The following figure shows the TM7ACTHA:

G-SE-0007209.1.gif

 

 

See also TM7ACTHA Characteristics and Wiring.