8055 Controller message HW monitor

Description

Refer to Diagnostic class (standard): 1

MsgFilter: Bit 14 Filter Type 15

Refer to the diagnostic messages 8056 Supply voltage low and 8827 Controller power-off/hardware monitor.

DiagMsg:

  • Specific diagnostic message for debugging purposes.

  • Structure: <last error entry> : <error group> : <cause of error>

Error groups:

  • VoltageError

  • TempError

  • EnvError

Cause of error (VoltageError):

  • V3.3 < Vmin

  • V5 < Vmin

  • V+12 < Vmin

  • V-12 < Vmin

  • Vin < Vshutd

  • VAccu < Vshutd

  • Vin_jit < Vshutd

  • capacitance

  • LTC error

  • Vin > Vmax

  • VAccu > Vmax

  • V3.3 > Vmax

  • V5 > Vmax

  • V+12 > Vmax

  • V-12 > Vmax

  • VcpuCore < Vmin

  • VcpuIO < Vmin

  • VM2.5 < Vmin

  • VM3.3 < Vmin

  • VM5 < Vmin

  • VM+12 < Vmin

  • VM-12 < Vmin

  • VcpuCore > Vmax

  • VcpuIO > Vmax

  • VM2.5 > Vmax

  • VM3.3 > Vmax

  • VM5 > Vmax

  • VM+12 > Vmax

  • VM-12 > Vmax

Cause of error (TempError):

  • Vin < Vmin

  • VAccu < Vmin

  • TAccu < Tmin

  • TLM75 < Tmin

  • TCPU < Tmin

  • TM1 < Tmin

  • TM2 < Tmin

  • TAccu > Tshutd

  • TLM75 > Tshutd

  • TCPU > Tshutd

  • TM1 > Tshutd

  • TM2 > Tshutd

  • TAccu > Tmax

  • TLM75 > Tmax

  • TCPU > Tmax

  • TM1 > Tmax

  • TM2 > Tmax

  • I2C bus failed

  • LM75 failed

Cause of error (EnvError):

  • fan1stop-shutd

  • fan1stop-off

  • fan2stop-shutd

  • fan2stop-off

  • fan3stop-shutd

  • fan3stop-off

Example of message text:

-1 : TempError : TLM75 > Tshutd

The error was in the last created error entry. It is a temperature error in which the LM75 sensor detected a temperature that is too high. The shutdown limit was exceeded, and so the system shut down after the timer ran out.