Refer to Diagnostic class (standard): 1
MsgFilter
: Bit 14 Filter Type 15
Refer to the diagnostic messages 8056 Supply voltage low and 8827 Controller power-off/hardware monitor.
DiagMsg
:
Specific diagnostic message for debugging purposes.
Structure: <last error entry>
: <error group>
: <cause of error>
Error groups:
VoltageError
TempError
EnvError
Cause of error (VoltageError):
V3.3 < Vmin
V5 < Vmin
V+12 < Vmin
V-12 < Vmin
Vin < Vshutd
VAccu < Vshutd
Vin_jit < Vshutd
capacitance
LTC error
Vin > Vmax
VAccu > Vmax
V3.3 > Vmax
V5 > Vmax
V+12 > Vmax
V-12 > Vmax
VcpuCore < Vmin
VcpuIO < Vmin
VM2.5 < Vmin
VM3.3 < Vmin
VM5 < Vmin
VM+12 < Vmin
VM-12 < Vmin
VcpuCore > Vmax
VcpuIO > Vmax
VM2.5 > Vmax
VM3.3 > Vmax
VM5 > Vmax
VM+12 > Vmax
VM-12 > Vmax
Cause of error (TempError):
Vin < Vmin
VAccu < Vmin
TAccu < Tmin
TLM75 < Tmin
TCPU < Tmin
TM1 < Tmin
TM2 < Tmin
TAccu > Tshutd
TLM75 > Tshutd
TCPU > Tshutd
TM1 > Tshutd
TM2 > Tshutd
TAccu > Tmax
TLM75 > Tmax
TCPU > Tmax
TM1 > Tmax
TM2 > Tmax
I2C bus failed
LM75 failed
Cause of error (EnvError):
fan1stop-shutd
fan1stop-off
fan2stop-shutd
fan2stop-off
fan3stop-shutd
fan3stop-off
Example of message text:
|
The error was in the last created error entry. It is a temperature error in which the LM75 sensor detected a temperature that is too high. The shutdown limit was exceeded, and so the system shut down after the timer ran out. |