Refer to Diagnostic class (standard): 3
|
Default reaction |
||
|---|---|---|
|
AD |
E |
|
|
- |
- |
|
|
AD |
- |
The Inverter Enable input is set to low, while the drive is enabled (AxisState >1) and parameter InverterEnableFunction is set to Safe Stop 1 / 1.
ControllerEnable, then the controller is active until the drive stops and the brake is engaged (BrakeCouplingTime). The maximum time for this stop is defined with the parameter StopTimeLim.
|
For the motor/drive system: |
|
|---|---|
|
Cause |
Solution |
|
Detected wiring error. |
Verify and correct if necessary the wiring of the Inverter Enable input. |
|
Detected circuit error: The Inverter Enable input is set to low. |
Verify and correct if necessary the control of the Inverter Enable input. |
|
The safety function |
Verify and correct if necessary the parameter InverterEnableFunction. |
The Safe Force Off (SFO) input is set to low, while the multi carrier segment is enabled.
|
For the Multi carrier transport system: |
|
|---|---|
|
Cause |
Solution |
|
Wiring error at the |
Verify the wiring and the control of the |
|
The communication interconnects are not inserted correctly. |
Verify the mounting and fastening of the communication interconnects of the multi carrier segments. |