Refer to Diagnostic class (standard): 2
Default reaction |
||
---|---|---|
D |
E |
|
D |
E |
|
D |
– |
The DC bus voltage is too high. A further increase can lead to the diagnostic message 8108 DC bus overvoltage.
Device |
Thresholds |
---|---|
Lexium 62 Power Supply |
|
The voltage threshold for this diagnostic message is only dependent on the parameter BrakingResistorMode. The parameter MainsVoltageMode has no influence on this threshold.
For information on causes and measures, see 8108 DC bus overvoltage.
The DC bus voltage of the multi carrier segment is too high (Udc > 60 Vdc).
For the Multi carrier transport system: |
|
---|---|
Cause |
Solution |
The settings of the rotary switches on the multi carrier connection module are incorrect. |
Set the rotary switches (P1, P2) of the connection module according to the information in the Lexium™ MC12 multi carrier Hardware Guide. |
Detected multi carrier hardware error: The segment is inoperative. |
Replace the multi carrier segment. |