8566 LMC connected to the incorrect port of the track

Description

Refer to Diagnostic class (standard): 3

The Sercos wiring is not correct. The P1 port (CN12) of the LMC (Logic Motion Controller) has to be connected to the P1 port of the track.

Refer to the wiring example for a closed track and the wiring example for an open track in the Lexium™ MC12 multi carrier Hardware Guide.

Cause

Solution

The Sercos wiring is not correct. The P1 port of the LMC (Logic Motion Controller) is not connected to the P1 port of the track.

Connect the P1 port of the LMC (Logic Motion Controller) to the P1 port of the track.