Assembling a Module to a Controller or Receiver Module

Introduction

This section describes how to assemble an expansion module to a controller, receiver module or other modules.

  DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION OR ARC FLASH
  • Disconnect all power from all equipment including connected devices prior to removing any covers or doors, or installing or removing any accessories, hardware, cables, or wires except under the specific conditions specified in the appropriate hardware guide for this equipment.
  • Always use a properly rated voltage sensing device to confirm the power is off where and when indicated.
  • Replace and secure all covers, accessories, hardware, cables, and wires and confirm that a proper ground connection exists before applying power to the unit.
  • Use only the specified voltage when operating this equipment and any associated products.
Failure to follow these instructions will result in death or serious injury.

After connecting new modules to the controller, either directly or through a transmitter/receiver, update and redownload your application program before placing the system back in service. If you do not revise your application program to reflect the addition of new modules, I/O located on the expansion bus may no longer operate normally.

 WARNING
UNINTENDED EQUIPMENT OPERATION
  • Only use software approved by Schneider Electric for use with this equipment.
  • Update your application program every time you change the physical hardware configuration.
Failure to follow these instructions can result in death, serious injury, or equipment damage.

Assembling a Module to a Controller or Receiver Module

The following procedure shows how to assemble a controller or receiver module and a module together:

Step

Action

1

Remove all power and dismount any existing controller I/O assembly from its DIN mounting.

2

Remove the expansion connector sticker from the controller or the outermost installed expansion module.

3

Verify that the locking device on the new module is in the upper position.

4

Align the internal bus connector on the left side of the module with the internal bus connector on the right side of the controller, receiver module or expansion module.

5

Press the new module towards the controller, receiver module or expansion module until it is securely in place.

6

Push down the locking device on the top of the new module to lock it to the controller, receiver module or previously installed expansion module.