Configure Binary Points for DNP3 Communications
The topics in this section document the properties on the Forms of SCADAPack x70 DNP3 Binary Points. You only require such points if Geo SCADA Expert is to use the DNP3 protocol to communicate with a SCADAPack x70 device and is to perform either of the following:
- Retrieve binary data from the SCADAPack x70 device
- Use a maintained control to set the values of binary data on the SCADAPack x70 device.
(To generate a pulsed, rather than a maintained, control, you use a Pulse Action rather than a Binary Point.)
Geo SCADA Expert uses the points to store protocol-specific information about how it processes the point data that it retrieves from, or sends to, the device.
For each item of binary data that Geo SCADA Expert is to retrieve from a SCADAPack x70 device using the DNP3 protocol, you need to create and configure a SCADAPack x70 DNP3 Binary Input Point in the database.
For each item of binary data for which Geo SCADA Expert is to set the values on a SCADAPack x70 device using the DNP3 protocol, you need to create and configure a SCADAPack x70 DNP3 Binary Output Point in the database.
Instead of manually creating a SCADAPack x70 protocol-specific Point, you can use the Create Protocol Point pick action to create the point from the <Point Type> Configuration item with which it is to be associated. This means of point creation will associate the Point automatically with the <Point Type> Configuration item from which the pick action was triggered. For more information, including essential checks to perform before using the pick action, see Create Protocol Point.
Alternatively, you can automatically create a suite of SCADAPack x70 protocol-specific Points for each of the SCADAPack x70 <Point Type> Configuration items that are associated with a particular SCADAPack x70 Device Configuration item. To do this, you use the separate Create Protocol Points pick action on that SCADAPack x70 Device Configuration item. Again, this means of point creation with associate each automatically-created Point with the SCADAPack x70 <Point Type> Configuration item to which it relates on the SCADAPack x70 Device Configuration item. For more information, including essential checks to perform before using this pick action, see Create Protocol Points.
You configure the properties of each Point using the fields on the SCADAPack x70 DNP3 Binary Input Point or SCADAPack x70 DNP3 Binary Output Point Form respectively. Each Form has several tabs, some of which contain properties that are common to many database items, and others that contain properties that are specific to Binary Points.
You can configure a SCADAPack x70 DNP3 Binary Input Point as a double-bit point by associating it with a pair of SCADAPack x70 Digital Configuration Items that use the appropriate DNP3 Static Group and Variations settings. For more information, see Specify the DNP3 Static Group and Variation, and see Common Properties on Points used for DNP3 Communications. When configured this way, each point consists of two bits, enabling four states.
This topic provides information about the properties that are on the Binary Point and Control tabs.
Use the Binary Point tab to:
- Configure the Common Properties on Points used for DNP3 Communications
- Configure the Binary Point States
- Configure Override Properties
- Configure the Trend Properties
- Configure Logged Data Properties.
The Forms of SCADAPack x70 DNP3 Binary Output Points also include a Control tab.
Use the Control tab to:
- Configure the Control Properties of a DNP3 Binary Output Point.
(The properties function in the same way as those on Binary Output Points on the parent DNP3 driver.)
The properties on the remaining tabs are common to points on many drivers. For information about those tabs, see Tabs on Point Forms in the Geo SCADA Expert Guide to Advanced Drivers.
Further Information