Configure the Event Attributes
The SCADAPack x70 tab on the Forms of SCADAPack x70 Digital Configuration items contains an Event Attributes section. Use the section to define the circumstances in which the SCADAPack x70 device generates point value-related events for the item. The properties only apply when using a communications protocol that supports, and is configured to enable, event generation. The properties also only apply when the SCADAPack x70 device is operating as an Outstation.
Use the Alert properties to prevent a change in value from affecting the point state until the point has been in that state for a specified time. Use the properties to reduce the requirement for the SCADAPack x70 device to needlessly report, and the SCADA system(s) to needlessly process, momentary changes of state.
The Event Attributes section includes these properties:
- Alert Set Time Deadband—Use to specify the amount of time that the digital's point state has to have continuously remained in the state defined by the Alert Active State before the alert state quality is indicated as on. If the digital is configured to do so (see Specify the Point Data Class used for DNP3 Communications), a DNP3 event is also generated to report the change of state to the DNP3 controlling station(s).
The deadband's time resets whenever the digital's point state reverts back to the point state that is considered the normal (non-alert) state.
You can specify a value between 0 and 65535 seconds inclusive. The default is 0 (resulting in no time deadband). Enter the required interval in the OPC Time Format. You can enter the value directly in the field, or use the Interval window (accessed via the field's browse button) to specify the required value.
- Alert Clear Time Deadband—Use to specify the amount of time that the digital's point state has to have continuously remained in the normal non-alert state (see Specify the Alert Notification Requirements) before the alert state quality is indicated as off. If the digital is configured to do so (see Specify the Point Data Class used for DNP3 Communications), a DNP3 event is also generated to report the change of state to the DNP3 controlling station(s).
You can specify a value between 0 and 65535 seconds inclusive. The default is 0 (resulting in no time deadband). Enter the required interval in the OPC Time Format. You can enter the value directly in the field, or use the Interval window (accessed via the field's browse button) to specify the required value.
If a DNP Class 0 Poll or DNP3 Level 3 Scan is performed during the Alert Set/Clear Time Deadband period, Geo SCADA Expert will log the changed state. The Alert Set/Clear Time Deadband settings determine whether the SCADAPack x70 device will generate a logged event. Use the Debounce Time (see Configure the Physical I/O Performance Properties) if you do not want the point state logged under such circumstances.
- Unsolicited Events (DNP3 Only)—Select this check box if the SCADAPack x70 device is to transmit the change of state events in an unsolicited message.
The unsolicited message might be sent immediately, or might be delayed according to the unsolicited message generation settings of the device.
Clear the check box (the default) if the device is not configured to send unsolicited messages, or is not to send such events as unsolicited messages. The SCADAPack x70 device will store the events in its internal Event Buffer until the SCADA system requests the data in a poll of the device.
Regardless of the check box's setting, the SCADAPack x70 device will timestamp each event with the time that the change in point state is deemed to have occurred.
For SCADA systems that are using the DNP3 protocol to communicate with the SCADAPack x70 device, the Unsolicited Events property only applies when the relevant 'Controlling Station Point Data Class' is set to Class 1, 2, or 3 Event on the Digital Configuration item's DNP3 tab (see Specify the Point Data Class used for DNP3 Communications).