The TM3 Ethernet bus coupler supports the following services:
oIPV4
oModbus TCP/IP server
The TM3 Ethernet bus coupler supports the following :
oTCP (Transmission Control Protocol)
oARP (Address Resolution Protocol)
oRSTP (Rapid Spanning Tree Protocol)
This table shows the maximum number of connections:
Connection Type |
Number of Connections |
---|---|
Modbus TCP/IP Server |
8 |
Ethernet/IP adapterEthernet/IP Adapter |
3 (Class 1): o1 Exclusive Owner o2 Listen Only 6 (Class 3) |
Web Server |
10 |
Each connection based on TCP manages its own set of connections as follows:
1.When a client tries to open a TCP connection that exceeds the poll size, the TM3 Ethernet bus coupler closes the oldest connection. For Class 1 and Class 3 connections, when a client tries to open a connection that exceeds the poll size, the TM3 Ethernet bus coupler denies the new connection with the message: no resource available.
2.If all connections are busy (exchange in progress) when a client tries to open a new one, the new connection is denied.
Connections can be closed when the originator of the connection requests to close the connection it had previously opened.