Refer to Diagnostic class (standard): 3
Default reaction |
||
---|---|---|
AD |
AD |
|
– |
– |
The encoder position could not be determined.
Cause |
Solution |
---|---|
Encoder voltage is incorrect or unavailable. |
Verify correct encoder voltage. |
Incorrect encoder cable or incorrect wiring. |
Verify correct wiring of the encoder with the correct encoder cable. |
The 24 Vdc control voltage is too low. |
Verify correct control voltage. |
Encoder inoperative. |
Replace the motor or the encoder. |
The following diagnostics messages provide additional information on the cause of this condition: