Configuring a DNP3 SCADAPack E Modbus Slave Device

You can connect a Modbus slave device to a DNP3 SCADAPack E outstation.

Before you can do this, you need to set up and configure a DNP3 SCADAPack E outstation (see Configuring DNP3 SCADAPack E Outstations)).

The SCADAPack E outstation must be running firmware version 8.12 or higher.

For each Modbus slave device that you connect, you need to add and configure a Geo SCADA ExpertDNP3 SCADAPack E Modbus Slave Device database item (see Add an Item to the Database). This section describes this database item.

You configure the DNP3 SCADAPack E Modbus Slave Device item by setting properties on its configuration Form. The Form has several tabs.This section describes how to configure properties on the Modbus tab. The tab properties are described below:

 

In the Communications section of the Modbus tab, you specify the settings for the connection between the SCADAPack E outstation and the Modbus slave device.

 

In the Scanning section of the Modbus tab, you can specify the settings that enable the SCADAPack E outstation to scan the Modbus slave device. Scanning is the process by which the SCADAPack E outstation reads the registers and coils on the slave device for any current data (a coil is a discreet single-bit register). The SCADAPack E outstation will retrieve and process any such data and then map it to DNP3 points. The data will not be stored in the Geo SCADA Expert database.

 

In the Data Concentrator Status and Control Points section of the Modbus tab, you can specify the points that:

The settings are as follows:

Further Information

Specify Whether Point Mapping is Used

Map to Point Data on a Modbus Master Scanner

Configure the Properties of the Individual Ports