TM241CEC24R logic controller has:
o14 digital inputs
o8 fast inputs
o6 regular inputs
o10 digital outputs
o4 fast outputs
o6 relay outputs (2 A)
oCommunication port
o2 serial line ports
o1 Ethernet port
o1 CANopen port
o1 USB mini-B programming port
The following figure shows the different components of the TM241CEC24R logic controller:
|
N° |
Description |
Refer to |
|---|---|---|
|
1 |
Run/Stop switch |
|
|
2 |
SD card slot |
|
|
3 |
Battery holder |
|
|
4 |
Cartridge slot |
– |
|
5 |
LEDs for indicating I/O states |
|
|
6 |
USB mini-B programming port / For terminal connection to a programming PC (EcoStruxure Machine Expert) |
|
|
7 |
Clip-on lock for 35 mm (1.38 in.) top hat section rail (DIN-rail) |
|
|
8 |
Embedded relay outputs |
|
|
Embedded fast transistor outputs |
||
|
Output removable terminal block |
||
|
9 |
CANopen Line termination switch |
|
|
10 |
100...240 Vac 50/60 Hz power supply |
|
|
11 |
CANopen port / Screw terminal block type |
– |
|
12 |
Ethernet port / Type RJ45 (RS-232 or RS-485) |
|
|
13 |
Status LEDs |
– |
|
14 |
TM4 bus connector |
– |
|
15 |
Serial line port 1 / Type RJ45 (RS-232 or RS-485) |
|
|
16 |
Serial line port 2 / Screw terminal block type (RS-485) |
|
|
17 |
Embedded digital inputs |
|
|
Input removable terminal block |
||
|
18 |
TM3/TM2 bus connector |
|
|
19 |
Protective cover (SD card slot, Run/Stop switch, and USB mini-B programming port) |
– |
|
20 |
Locking hook (Hook not included) |
– |
The following figure shows the status LEDs:
1 System status LEDs
2 Cartridge status LEDs (optional)
3 I/Os status LEDs
The following table describes the system status LEDs:
|
Label |
Function Type |
Color |
Status |
Description |
||
|---|---|---|---|---|---|---|
|
Controller States1 |
Prg Port Communication |
Application Execution |
||||
|
PWR |
Power |
Green |
On |
Indicates that power is applied. |
||
|
Off |
Indicates that power is removed. |
|||||
|
RUN |
Machine status |
Green |
On |
Indicates that the controller is running a valid application. |
||
|
Flashing |
Indicates that the controller has a valid application that is stopped. |
|||||
|
1 flash |
Indicates that the controller has paused at BREAKPOINT. |
|||||
|
Off |
Indicates that the controller is not programmed |
- |
- |
|||
|
ERR |
Error |
Red |
On |
An operating system error has been detected. |
Restricted |
No |
|
Fast flashing |
The controller has detected an internal error. |
Restricted |
No |
|||
|
Slow flashing |
Indicates either that a minor error has been detected, if the RUN LED is illuminated, or that no application has been detected. |
Yes |
No |
|||
|
I/O |
I/O error |
Red |
On |
Indicates device errors on the embedded I/Os, serial line 1 or 2, SD card, cartridge, TM4 bus, TM3 bus, Ethernet port or CANopen port. |
||
|
SD |
SD card access |
Green |
On |
Indicates that the SD card is being accessed |
||
|
BAT |
Battery |
Red |
On |
Indicates that the battery needs to be replaced. |
||
|
Flashing |
Indicates that the battery charge is low. |
|||||
|
SL1 |
Serial line 1 |
Green |
On |
Indicates the status of serial line 1 |
||
|
Off |
Indicates no serial communication |
|||||
|
SL2 |
Serial line 2 |
Green |
On |
Indicates the status of serial line 2 |
||
|
Off |
Indicates no serial communication |
|||||
|
TM4 |
Error on TM4 bus |
Red |
On |
Indicates that an error has been detected on the TM4 bus |
||
|
Off |
Indicates that no error has been detected on the TM4 bus |
|||||
|
ETH |
Ethernet port status |
Green |
On |
Indicates that the ethernet port is connected and the IP address is defined. |
||
|
3 flashes |
Indicates that the ethernet port is not connected. |
|||||
|
4 flashes |
Indicates that the IP address is already in used. |
|||||
|
5 flashes |
Indicates that the module is waiting for BOOTP or DHCP sequence. |
|||||
|
6 flashes |
Indicates that the configured IP address is not valid. |
|||||
|
CAN R |
CANopen running status |
Green |
On |
Indicates that the CANopen bus is operational. |
||
|
Off |
Indicates that the CANopen master is configured. |
|||||
|
Flashing |
Indicates that the CANopen bus is being initialized. |
|||||
|
1 flash per second |
Indicates that the CANopen bus is stopped. |
|||||
|
CAN E |
CANopen error |
Red |
On |
Indicates that the CANopen bus is stopped (BUS OFF). |
||
|
Off |
Indicates no CANopen detected error. |
|||||
|
Flashing |
Indicates that the CANopen bus is not valid. |
|||||
|
1 flash per second |
Indicates that the controller has detected that the maximum number of error frames has been reached or exceeded. |
|||||
|
2 flashes per second |
Indicates that the controller has detected either a Node Guarding or a Heartbeat event. |
|||||
1 For more information about the controller state description, refer to the M241 Logic Controller - Programming Guide.
The following figure shows the external dimensions of the logic controller: